2.4 Instruction Details
1
2
3-83
Chapter 2 Instructions
Operands
* Note that of I/O Nos. 7000 to 9915, those that are not assigned to expansion or remote I/O
unit ports can be used for internal utility relays.
Key operation
Applications of SFT instruction
Alternating circuit
Every time input relay No. 0000 turns ON, 0500 turns alternately ON and OFF.
Coding
Timing diagram
Reference: Alternating circuit can be configured without SFT instruction.
The following circuit does the same operation as the circuit above.
"DIFU instruction" (p. 3-78)
Coding
1000
0000
2003
1000
0500
SFT
D
1000
CLK
1000
RES
Line No. Instruction Operand
0000 LDB 1000
0001 LD 0000
0002 LD 2003
0003 SFT 1000 1000
0004 LD 1000
0005 OUT 0500
ON
OFF
ON ON ON ON ON
0000
0500
Line No. Instruction Operand
0000 LD 0000
0001 DIFU 1000
0002 LD 1000
0003 ANB 0500
0004 LDB 1000
0005 AND 0500
0006 ORL
0007 OUT 0500
SFT
FUN
OR
9
ORL
3
Operand
(Relay No.)
Operand
(Relay No.)
ENT
R-SRCH
ENT
R-SRCH
0000
1000
DIFU
1000
1000
0500
0500
0500
Visual KV KV-300 KV-10/16 KV-24/40/80
1000 to 1915 1000 to 1915 1000 to 1915 1000 to 1915
3000 to 6915 3000 to 6915 3000 to 6915
*7000 to 9915
KVNKA Chap 02_4aP.p65 08.3.11, 11:58 AM83